High-voltage test simulator for HVDC cables, in the browser.

Open the simulator

What HCTS is

HCTS is a free, browser-based simulator of high-voltage laboratory tests on HVDC cables. It models the Marx impulse generator, the cable as a lossy transmission line, the measuring divider and the acquisition chain, and evaluates the recorded waveform according to IEC 60060-1:2025.

Designed for high-voltage laboratory engineers, cable manufacturers and students: it helps to size the test circuit for large capacitive loads such as long cables and to understand how the generator and the measuring system affect the evaluated parameters.

Frequently asked questions

Is HCTS free? Do I need an account?

Yes. HCTS is free and needs no registration or installation: it runs in any modern browser on computers, tablets and smartphones. It can also be installed as an app and used offline.

Which high-voltage tests does it simulate?

Impulse tests on cables: lightning impulse (LI, standard 1.2/50 µs shape) and switching impulse (SI, 170/2500 µs according to IEC 60060-1:2025), with positive or negative polarity, and superimposed tests in which the impulse is added to a DC (HVDC) voltage already applied to the cable: SLIT (superimposed lightning impulse) and SSIT (superimposed switching impulse), as specified for HVDC cable systems (for example CIGRE TB 496 and IEC 62895). It also simulates the DC routine test with a breakdown, described below.

How are U_t, T1, T2 and the overshoot β′ evaluated?

According to IEC 60060-1:2025: a double exponential (base curve) is fitted to the record, the residual is filtered with the test voltage function k(f) = 1/(1 + 2.2·f²) and added back to the base curve to obtain the test voltage curve. From it the test voltage value U_t, the front time T1 = 1.67·(t90 − t30) and the time to half value T2 from the virtual origin O1 are derived; the overshoot is β′ = (U_e − U_b)/U_e. Every quantity is checked against the tolerances of the standard. If the base curve cannot be determined or the record is clipped, the values are reported as not evaluable instead of being computed on the raw record.

Which circuit is simulated?

An N-stage Marx impulse generator (stage capacitors in series or in parallel, front, tail and charging resistors, internal inductance, optional parallel stages, tail resistors that may differ from stage to stage), the inductances and capacitances of the connections, the cable under test as a lossy transmission line (DC resistance of conductor and metallic screen and skin effect computed from the cable geometry), the measuring divider (resistive, capacitive, damped capacitive or compensated mixed RC for DC and impulse, the default) and the acquisition chain with low-pass filter and ADC. For superimposed tests the DC source and the blocking element are included: a capacitor or a fixed-spacing sphere gap that sparks over only when the voltage across it exceeds its sparkover voltage. The circuit diagram with the values set is shown above the plots and included in the PDF report.

What does the DC routine test calculate?

The overvoltage that follows a breakdown during the DC routine test of a cable drum: the cable is charged at the test voltage and the arc at the outdoor termination, at the terminations in the back-to-back box or at the blind joint discharges it. The waves travelling along the cable piece and the drum bring the opposite end to a voltage of opposite polarity (plateau, about U·(1 − 2k)), with overshoots caused by the head circuit. HCTS computes the plateau with an analytic formula and with the simulation, the voltage excursion on the drum, the electric field at the inner and outer semiconductive screens after the reversal, the maximum peak along the drum and the voltages at the termination, the back-to-back box, the blind joint and the HV pole. The peak above the plateau depends on data that are often estimated (HV pole, termination and back-to-back box capacitances, arc collapse time): the “Peak range in the drum” button repeats the calculation varying them and gives the range to report.

What is the “Generator resistors” tool for?

To decide how to mount the front or tail resistors with those available in the laboratory: given the number of stages, the minimum to use, how many resistors can be placed in parallel in a stage and the values with their quantities, it finds the arrangement with the lowest total resistance or the one closest to a required value, for each number of stages. The stages can be required to be all identical, to use at most two different arrangements, or be left free; each solution also shows the load of the most stressed resistor relative to the mean. From the generator section the result is applied directly to the simulator to see its effect on the waveform.

What is the “Air clearances” tool for?

To estimate, before starting a test, the minimum air clearance between energised parts and parts at a different potential, usually earth, to avoid flashover. You choose the voltage (DC, AC, lightning or switching impulse, superimposed DC + impulse tests) with its value, the geometry (gap factor K, from rod-plane, the worst case, to smooth conductors), the laboratory temperature, pressure and humidity, and a margin on the voltage (default 1.2). The calculation uses the breakdown voltages of IEC 60071-2 (for DC a typical literature value), the atmospheric correction of IEC 60060-1, never credited beyond the standard atmosphere, and a flashover probability of about 0.1 %. The “Use the current test” button takes test type and voltages from the simulation. It is a supporting estimate: it does not replace the laboratory safety rules or EN 50191.

What is HCTS used for in practice?

To prepare and understand laboratory tests: choose the number of stages, the capacitors and the resistors of the generator to obtain the standard waveform on a large capacitive load such as a long cable, estimate the generator efficiency (impulse peak / Marx voltage), see how the measuring system affects the evaluated parameters and estimate the overvoltages after a breakdown in the routine test. It is also useful for training. Results are an estimate: they do not replace the test or the review of an expert.

Is my data sent to a server?

No. All calculations run in the browser, on the device; parameters and configurations stay local until you export them. Visit statistics (Google Analytics) are enabled only with explicit consent.

Who develops HCTS?

HCTS was conceived by Marco Moraschi, an electrical engineer, and is developed by backohm (backohm.com). Reports and suggestions are welcome at hello@backohm.com.